| Opvarmet boligareal (m²) | 75% dækning – boliger efter 1985 (Kedelydelse kW) | Boliger bygget efter 1985 (Kedelydelse kW) | Boliger bygget før 1920 (Kedelydelse kW) |
|---|---|---|---|
| 100 | 6 | 10 | 16 |
| 200 | 13 | 16 | 31 |
| 300 | 17 | 24 | 45 |
| 400 | 23 | 30 | 60 |
| 500 | 28 | 37 | 75 |
| 600 | 33 | 45 | 90 |
Kilde: Teknologisk Institut, Installationsvejledning for biobrændselskedler, oktober 2000
Calculate based on oil consumption
Calculate based on gas consumption
Find boiler size based on housing type
Find boiler size based on the home’s floor area and age
To select the right boiler size, you can either base it on your annual oil or gas consumption or – if the consumption is unknown – on the size and age of the home
The table helps you find the boiler output that matches both modern, well-insulated homes and older houses with greater heat loss.
We have included an additional heat demand of 2 kW for domestic hot water, so the result is more realistic.
If you have an oil boiler in the system, it can be used as a backup during peak load, which allows the boiler to be sized down to around 75% of the total heat demand.